Larger
systems are custom designed for
villages and small cities'
applications reaching the
multi-hundred thousands cubic meters
per day capacities.
|
 |
The
above specifications are based on
the following:
|
|
- |
U.S.
Corps of Engineers and the United
States EPA Guidelines for Extended
Aeration Systems.
|
|
- |
Peak
Flow at 3 times the average flow.
|
|
- |
Raw
sewage from human waste (For
industrial waste streams, please ask
about EBD industrial wastewater
treatment systems).
|
|
- |
Raw
sewage parameters of 240 ppm BOD and
300 ppm S.S. (BOD up to 400
ppm and SS of 500 ppm can be treated
with certain system modification).
|
|
- |
Twenty
Four (24) hours retention time in
the aeration tank [ Design ranges
from 18 to 36 hours based on BOD
levels].
|
|
- |
Two
streams operation to provide
flexibility, handling low flows and
improving efficiencies.
|
|
- |
Gravity
clarifiers with 1.5 m³/m²/hr rise
rate [Design ranges from 1.0 to 1.8
m³/m²/hr] and 4 hours
retention time [Design ranges from 3
to 4.5 hours].
|
|
- |
Aerated
Sludge digestion tank for 15 days
retention time.
|
|
- |
Chlorine
contact tank for 45 minutes
retention [design ranges from 30 to
90 minutes].
|
 |
Electric
characteristics: 230/460 V, 3 PH, 60
HZ as standard [380 V, 3 PH, 50 HZ
available].
|
|
|
|
|
Below
ground or above ground installation
is possible. Welded steel
packages are provided with magnesium
anodes for cathodic protection.
|