3/4 

Selective Data

MODEL FLOW RATE
Primary


(gpm)
FLOW RATE
Polishing


(gpm)
Total
Resin
Volume
Primary
(ft³)
Total
Resin
Volume
Polishing
(ft³)
Tank dia.



(in.)
Pipe Size
Primary


(in.)
Pipe Size
Polishing


(in.)
IED-24 30 40 12.4 12.4 24 1 1/2 1 1/2
IED-30 50 70 19.4 19.4 30 1 1/2 1 1/2
IED-36 70 100 31.0 33.0 36 2 1/2 3
IED-42 90 140 43.0 41.0 42 2 1/2 3
IED-48 120 180 57.0 42.0 48 3 3
IED-54 150 230 73.0 53.0 54 3 4
IED-60 180 280 90.0 66.0 60 3 4
IED-66 230 340 110.0 81.0 66 3 4
IED-72 270 410 132.0 97.0 72 4 6
IED-84 370 560 182.0 135.0 84 4 6
IED-90 430 640 212.0 155.0 90 6 8

  

Notes: 1. 

The resin ratio, anion to cation is selected as required.

2. 

Standard tanks for primary demineralization are 8'0" straight height while polishing demineralization are 6'0" straight height.
Optional 6'0" straight height primary demineralizer is also available.
 

Instrumentation and Controls

The EBD Water IED Demineralizers are automatically controlled by solid state Programmable Logic Controllers (PLC) in conjunction with pilot solenoid valves or stagers.  The pilot solenoid valves and the stagers can be provided with manual by-pass.  The controller is capable of controlling individual or multiple regenerations.  A resistivity controller monitors the quality of treated water and initiates the regeneration sequence.  Silica analyzer can also be provided as an option.

The following controlling instruments are installed within the IED Systems:
 

Rate of flow indicator for water and air.
Resistivity monitor.
Automatic reset totalizing water meter (option).
Electrical interlock for multiple units.
PC based monitoring and control system (option)

 

BRACKISH WATER REVERSE OSMOSIS

SEAWATER REVERSE OSMOSIS

SEWAGE TREATMENT

INDUSTRIAL WASTEWATER TREATMENT

ION EXCHANGE DEMINERALIZATION

WATER SOFTENING

PRESSURE FILTRATION

CHEMICAL FEED SYSTEMS
Gas and Liquid Feeders